Description
This device is designed to detect the presence of fire inside residential or commercial buildings. It should not be installed in industrial premises. The battery-powered detector has a built-in local warning siren combined with a red LED indicator.
The detector combines an optical smoke sensor with a heat sensor. Both sensors have their outgoing signals processed digitally, resulting in higher false alarm immunity. The optical sensor works using a light diffusion principle and is very sensitive to the presence of large-sized particles which are characteristic of dense smokes. By contrast, the sensor is less sensitive to small-sized particles which are typical of cleanly burning fires. In particular, the smoke sensor is not capable of detecting the by-products of cleanly-burning fluids such as alcohols, for instance. This deficiency is compensated for by the built-in heat sensor. This sensor provides a slower reaction when compared to the smoke sensor, but is much better at reacting to fires with rapidly rising heat producing only a little smoke. Smoke/heat sensor participation is configurable by DIP switches.
|
Technical information
- Voltage: 1x AA 1.5 V alkaline battery;
-
Battery lifetime: typically 2 years;
-
Smoke sensor sensitivity: m = 0.11 - 0.13 dB/m;
-
Fire-alarm temperature: +60 °C to +70 °C;
-
Acoustic power of the built-in siren min: 85dB/3m A;
-
Operational temperature range: -10 to +70 °C;
-
Dimensions: diameter 126 mm, height 65 mm
|